Protection Philosophy

Operating Principle

Industrial electrical enclosures feature permanent ventilation openings, cable penetrations, and technical gaps that make long-term airtightness unrealistic. We therefore adjust the extinguishing agent quantity to compensate for leakage. Fire outbreaks are detected at the ignition source, and a dry contact output is made available after activation to disconnect the main power supply and secure your installations.

The Reflexofeu Solution

An approach specifically designed for real industrial operating conditions

1

Detection

Abnormal heating detected by tube or thermal head

2

Activation

Pressure drop and mechanical opening of the valve

3

Diffusion

FK-5-1-12 diffused directly onto the risk zone

4

Securing

Automatic securing, extinguishing in less than 3 seconds

Detection at the Core of the Components

Direct detection at the heart of high-risk components, independent of enclosure airtightness.

Linear Heat Detection Tube

Linear thermal detection tube

Linear thermal detection tube

Continuous detection along the entire length

The tube ruptures at the exact location of the fire, triggering targeted extinguishing.

Mechanical activation without electricity

Autonomous operation, independent of any electrical power supply or control panel.

Flexible and modular installation

Adapts to all volumes and configurations of electrical cabinets.

Point-Type Thermal Bulb

Point thermal detection head

Point thermal detection head

Precisely calibrated temperatures

Triggering at predefined thermal thresholds, adapted to each application.

Targeted detection on high-risk components

Direct positioning on hot spots: variable speed drives, batteries, busbars.

Rapid on-site installation

Simple assembly without works, compatible with cabinets in service.

FK-5-1-12 Clean Agent

Clean gaseous agent, residue-free, electrically non-conductive, fully compatible with energized electrical equipment.

Technical characteristics

  • Non-conductive, compatible with energized equipment
  • Residue-free, no post-intervention cleaning required
  • Extinguishing in less than 3 seconds
  • Concentration: 4.5% to 5.3% by volume

Environmental impact

  • Global warming potential: GWP = 1
  • Atmospheric lifetime: 5 days
  • Zero impact on the ozone layer (ODP = 0)
  • No risk to groundwater
  • Compliant with European F-Gas regulation

Localized Suppression Independent of Airtightness

Immediate system isolation through automatic disconnection of power supply and ventilation. The system acts directly on the hazard zone without depending on overall enclosure airtightness.

Measured results

  • Fewer production stoppages
  • Less material damage
  • Truly operational fire safety

Limitations of classic volumetric calculation

Traditional calculation methods (NFPA / EN) assume a sealed volume, absence of ventilation and stability over time.

These assumptions are not compatible with an industrial electrical cabinet.